FDC location on grid fire sprinkler system? 3 - Eng-Tips
2002年2月26日 · The FDC is located on the front of the building. It is a single 2 1/2" connection fed with 2" pipe from the secondary 2" main. To be clear - all mains, wet riser, and FDC feed piping are 2" sch 40. All gridded branchlines are 1 1/4" sch 40.
Multiple fire risers and multiple FDC's - NFPA (fire) Code Issues
2005年2月7日 · There would be one FDC located at the pump room. The FDC would charge the entire site fire line, thereby charging all of the hydrants and risers/systems. The 3-way suction line hydrant is located adjacent to the FDC and upstream of the pump. This allows the FD to connect to a pumper connection on the hydrant and then go to the pump on the truck.
free standing FDC drainage with no basement - Eng-Tips
2012年10月23日 · Install a small 3' dia pre cast manhole with an open bottom close to the FDC. Line with gravel. Bury piping below freeze line and extend pipe upstream of the FDC sloped slightly toward the manhole and provide a ball drip. Put a lid on the manhole for access and inspection of ball drip.
Fire Service Piping at a Building - Eng-Tips
2005年10月20日 · Does anyone know where I might find a general schematic layout (or provide one here with an explanation) of the fire service piping at a building? Specifically, showing the relative locations of the water main, BFP, PIV, FDC, sprinkler riser, and any other appurtenances.
NFPA 13 Code question - Fire Department Connection - Eng-Tips
As per 2007 edition, 8.17.2.4.2 says the FDC shall be on the system side of system control, check and alarm valves (wet systems). 8.17.2.4.4 then says the requirements of 8.17.2.4.2 and 8.17.2.4.3 shall not apply where the fire department connection is connected to …
Manual dry standpipe FDC / Why a check valve? 2 - Eng-Tips
2006年11月30日 · I have a manual dry standpipe, it's the only one I've ever done in my life the reason being most jurisdictions I've worked in never allowed dry manual standipipes, and I just got approved drawings back with a note requiring a 6" check valve with ball drip between the 3 …
The issue of not having a shut off valve in the fire department ...
2006年11月30日 · 5.9.3.2 No shutoff valve shall be permitted in the piping from the fire department connection to the point that the fire department connection piping connects to the system piping. In the 2010 edition of NFPA 13, annex figures were added to clarify that the no shutoff valve requirement applied to the fire department connection piping. (A.8.17.2 ...
What is the purpose of drain valve in fire department connection ...
2018年12月7日 · The piping between the check valve and the outside hose coupling shall be equipped with an approved automatic drip in areas subject to freezing. Comment Section on the above. In the event that the check valve in the Siamese connection leaks, the purpose of the automatic drip is to drain this water to a safe location and to maintain the piping ...
Can you pump into a test header on a fire pump to feed the system?
2009年4月4日 · My understanding is that you are not allowed to put a shut off valve in the FDC piping (see NFPA 13 2007 section 8.16.1.1.1.3). The logic being that the FDC is going to be used in an emergancy situation and in that case they don't want to take a chance that a valve would prevent water getting into the distribution system.
Fire Department Connections on systems with zones at both riser …
2015年8月25日 · We have many where there is a site FDC that pumps up the underground and goes to various zones or buildings? NFPA 13 states that there are to be no shut off valves in the FDC piping. Yet, there is an exception for FDC attached to underground and FDC attached to a header. 8.17.2.4.3 is the section that describes exactly as your sketch shows.