HFC cable | Information by Electrical Professionals for Electrical ...
2014年2月3日 · HFC cable. Thread starter dpatel612; Start date Feb 3, 2014; Status Not open for further replies. D. dpatel612
HCF cable | Information by Electrical Professionals for Electrical ...
2020年10月8日 · What the manufacturer I linked calls HFC appears to be type AC cable with a green insulated conductor. The sheath counts as a ground, just like any AC cable, and the green insulated conductor is a ground. That looks like a redundant ground to me. Jon
"Snap2it" connectors and HFC Cable | Information by Electrical ...
2018年8月30日 · Zinc die-cast. For AC · MCI-A · HCF steel and aluminum cable · Flexible metal conduit steel and aluminum (regular and reduced wall) · MCI cable Continuous corrugated aluminum · AC90. For additional information, including specifications, dimensions, and applications - please click on a part number listed below.
HFC MC Cable | Information by Electrical Professionals for …
2008年3月31日 · I have a servcie call to install 2 oultetls in a doctors office. the office for which these outlets are to beinstalled were prviouslly used as exam rooms but know are used as an office. 2 questions. 1. I was quoted 198.00 for a roll of …
HCFC termination | Information by Electrical Professionals for ...
2010年10月21日 · The small strip in the BX and HFC cable is just a bonding strip. It shorts the turns of the cables jacket so it is like one piece of metal instead of a giant coil. It can be cut flush when you strip the jacket.
HCF cable | Information by Electrical Professionals for Electrical ...
2021年6月28日 · I have #8 HCF cable on plans for patient care areas fed from 40A branch circuit breaker. I have been told HCF cable comes with insulated EGC by manufacturer. What would be the min size equipment grounding conductor for HCF cable provided by the manufacturer?
Type MC Cable in Patient Care Areas - NEC 517
2017年12月20日 · It is my opinion that Type MC cable must be specifically listed for this application, as all MC cable does not meet the requirements below: NEC Refernence Article 517 of the National Electrical Code (NEC) states that "(NEC 517) Part II applies to patient care space of all health care facilities.”
bonding strip in HCF-LITE cable | Information by Electrical ...
2015年2月4日 · How do you properly terminate the extra bonding strip in HCF-Lite cable for healthcare applications.I have seen them wrapped back around the outer sheath of the cable,cut off at the end of the sheath and connected to all other grounds in the box and landed. What is the proper method of terminating the bonding strip?
Armor Cable, MC, AC, BX etc. | Information by Electrical …
2010年3月13日 · MC cable has a full size ground wire the casing is not a grounding conductor. MC can also be listed for wet location use where BX can not. MC is also availible as HFC cable which has a bonding strip as well as a full sized ground. This cable can be used in a patient care area or for an isloated ground circuit. Does this clear thing up?
flexible metal conduit in critical branch circuit
2019年3月29日 · My question is can HFC/AC cable be used for circuits served by critical branch. Is there a limit as to the length of the run in the use of the hospital grade MC cable. They are running exposed across drop ceilings instead of conduit some runs are 25’ long.