Securing MC Cable | Information by Electrical Professionals for ...
2025年2月7日 · For MC Cable, PI No. 2883-NFPA 70-2023 reads almost identical to the PI on NM cable, just with the name changed. You could still use tie wire if UL 2239 has standards for tie wire. You'll just need to get UL 2239 listed tie wire. I'll leave it to you to check UL 2239 on what it has to say on the topic. Cheers, Wayne
MC/BX/AC, please clarify. Also, what cut and bush do you use?
2024年11月14日 · AC is armored cable made with paper individually wrapping the conductors and a thin aluminum bonding strip which with the armor serves as the EGC. BX is a slang name for AC. Metal Clad or MC cable is different. Regular MC has a green EGC, MC-ap has a #10 aluminum conductor in contact with the armor to create the EGC.
AC vs MC Cable | Information by Electrical Professionals for …
2011年10月28日 · AC cable typically has no ECG, just the bondstrip-and-cable armor. However, the armor of the AC cable can be used as an ECG. MC cable consists of an outer jacket of thin metal armor and is filled with individually insulated conductors which are contained in a jacket. MC cable has an ECG, but the armor isn't suitable for grounding.
MC cable firestopping UL interpretation | Information by Electrical ...
2024年11月19日 · 1) You can use _any_ MC cable up to a maximum of 3C+ground #8 AWG. 2) You can use an MC cable classified under the 'through penetrating products' category. When I did a search for 'through penetrating products' I found datasheets for various firestop assemblies, and those datasheets specified the specific MC cable they were listed with.
AC vs. MC vs. MC Lite | Information by Electrical Professionals for ...
2003年3月21日 · Re: AC vs. MC vs. MC Lite Spelling it out in a spec is the easy part. Sometimes chnages in contract occur without detailing each item, such as the type MC (or steel compression couplings vs cast). I was curious if Type MC automatically covered the steel aspect, or is no MC spec complete without a steel or aluminum choice.
100 Amp MC Cable | Information by Electrical Professionals for ...
2014年4月25日 · I need to run a three phase, 3 wire feeder to a rooftop chiller that requires 100 amps, 480 volts. The ceiling below the unit is very congested so I hope to run MC cable in lieu of conduit and wire. I will run to a JB below the roof and switch over to liquid tight from threre through the pitch pocket. Do they make 3-3 copper MC cable?
Supporting MC Cable | Information by Electrical Professionals for ...
2013年6月8日 · Type MC cable that runs horizontally through or on framing members or racks (spaced less than 6 ft apart) without additional securing is considered supported. Staples or cable ties are not required as the cable passes through or on these members. However, the MC cable must be secured (fastened in place) within 12 in. of the outlet box.
EMT vs MC | Information by Electrical Professionals for Electrical ...
2010年9月7日 · I was taught that, in concealed work, for the most part running MC is more efficient than EMT. With MC you have both raceway and conductors installed in one shot. Say I was hypothetically quoted 100 feet of ? EMT @ almost thirty bucks Fittings (couplings, connectors, unistrut clips) came out...
MC Cable Labor | Information by Electrical Professionals for …
2023年10月18日 · 12/2 MC Steel Armor w/ supports and connectors Generally speaking here regarding install . Me and a friend have pretty different labor units per thousand. Standard height ceiling, ceiling not installed yet. Supported either a bridle ring on flange, or KX clip on rod by others. 500' with 15...
anti-short bushings | Information by Electrical Professionals for ...
2005年2月26日 · The confusion stems from the fact that some MC cable manufacturers include anti-short bushings with their cable. The inclusion of anti-short bushings with coils or reels of MC cable is based on historical practice relating to the requirements of 320.40 of the NEC, which mandates the use of anti-short bushing or its equivalent protection for ...