Bad outdoor txv? - HVAC-Talk
2015年12月20日 · New outdoor txv fixed it. Must have been stuck completely shut, wish I could tell you why, I've been wondering what has been causing all the txv failures recently. I've done 3 and have a 4th outdoor txv replacement coming this week.
TXV Valve - Indoor and Outdoor? - HVAC-Talk
2008年10月18日 · My 1 year-old Goodman GSH14036 heat pump has a TXV on the indoor coil for a/c mode and a TXV on the outdoor coil for heat pump mode. Reply 10-20-2008, 06:14 PM #5
Outdoor TXV? - HVAC-Talk
2012年11月3日 · Suction line temp at TXV bulb / before accumulator – 44 Suction line temp at compressor / after accumulator – 4 (?) Frost forming immediately on outdoor distributors and on coil after about 5 minutes Some things that don’t make sense to me but I’m pretty certain that the TXV is restricted. Bulb position was correct and well insulated.
TXV on outdoor unit - HVAC-Talk
2023年6月6日 · You’re better off getting a GSZ14 outdoor unit ( and saving upfront money vs the GSZ16 ) and a CA*F cases coil with field TXV as the SEER rating is the same at 14. You don’t go by the rating of the outdoor unit alone to get SEER/SEER2 …
Trane heat pump outdoor txv - HVAC-Talk
2016年3月23日 · Leaning towards problem with the outdoor txv but was looking for some advice from anyone with expirience on this thanks for any help. Reply 03-23-2016, 08:39 PM #2
heatpump bad txv or restriction - HVAC-Talk
2014年6月13日 · Check for temp drop across the filter drier, shouldn't be more than 2-3deg. If that checks OK recover the refrigerant, open up the system and check the TXV strainer, the outdoor piston metering device (both should just be a nut connection, no brazing), the liquid line piping (for kinks), and check for acid in the system (smell or pH test).
Goodman 2 Stage Heat Pump Adjustable TXV - HVAC-Talk
2022年11月28日 · IMO, leave the outdoor metering device alone, you got the final field refrigerant charge to manufacturers specifications in cool mode. Don’t go messing with the outdoor metering device. I’d like to see a photo of the indoor TXV as well as the outdoor TXV bottom part mainly as I always thought those metering device where non adjustable.
Heat Pump TXV Problem - HVAC-Talk
2021年3月23日 · Do the line temps make sense. I had a heat pump that looked like a bad outdoor TXV, but I was only looking at pressures, then I looked at the SH/SC, didn't make sense at first, then it did. I was right and wrong at the same time, it was the TXV, but not outside, inside. The inside TXV was biflow, it was bad so it was metering both ways.
Carrier Infinity 25HNA -- why no outdoor TXV - HVAC-Talk
2009年4月13日 · A TXV, be it installed at the indoor or outdoor coil (or both) is a superheat control device doubling as a metering/expansion instrument. The fixed orifice meters only, with rate of metering determined by pressure drop across the orifice.
Heat pump txv - HVAC-Talk
2014年3月11日 · The reversing valve is located in the outdoor unit, the discharge line enters the reversing valve, there are three outlets, in heating mode the hi pressure hi temp super heated Vapour travels to the indoor unit to heat the house, the indoor coil rejects the heat to the house and condenses the refrigerant and it flows back to the outdoor unit ...