Should I use SER or URD cable for a 100 amp sub-panel?
2020年7月10日 · If the cable is SER and not also USE or URD then it is not permitted underground. THHN is not wet location rated, underground is wet location even in conduit, but most THHN cable is also rated THWN, which is wet location rated. THWN or XHHW would be fine in conduit for all the circuit conductors.
Type USE cable or URD Cable | Information by Electrical …
2015年3月24日 · From everyone I talked to a lot of cable today know as URD is listed for use as USE or USE-1 it also carries other listings such as RHH and RHW-2 with flame retardant properties. This has been confusing since I kept getting different information from different suppliers from their understanding of the manufactures specifications on the cable ...
URD cable for underground feeder to home? | Information by …
2005年4月18日 · URD is just a type of USE cable that has 3 or 4 conductors twisted together. You will have a very hard time getting this into 2 inch schedule 80 conduit. See chapter 9 Fine Print Note #2 concerning jamming criteria. #6 and larger USE alledgedly has the same insulation thickness as THW.
URD cable and the NEC | Information by Electrical Professionals for ...
2010年9月9日 · My question is ... will the NEC allow URD Cable to be direct burial and terminated directly into a Service Panel on the inside of a building or will you have to transition on the outside of the building and bring another type cable into the panel . Thanks for your ideas:
urd/use cable to subpanel | Information by Electrical Professionals …
2006年9月7日 · im putting a 100 amp subpanel into a dettachted garage and i figured with copper prices i would use 1/0, 1/0, 2 urd/use aluminum cable to feed the panel instead of pipe and copper conductors. the problem is that im having a hard time finding it in a 4 conductor cable(2 hots, 1 neutral, 1 ground).
Ampacity of URD | Information by Electrical Professionals for ...
2019年9月25日 · It seems a cable could overcome 31.8% overload in cable duct for 4 hrs.-for instance- but transformer only 5%. See IEEE 5796/1993 Table 6 compare with IEEE 242/2001 9.5.2 Overload capacity[for cable]. I thought if one intends to replace the actual transformer with another larger and keep the secondary cable.
URD cable | Information by Electrical Professionals for Electrical ...
2009年10月26日 · True URD cable isn't a recognized NEC insulated conductor and should be used only by POCOs. I believe there are products that carry the dual rating of URD/USE. These are acceptable NEC wiring methods but per 338.12 must terminate on the exterior of the building (usually at a meter socket or j box)
One more time: USE-2 indoors? and, in conduit, or exposed?
2017年3月2日 · We get a lot of URD cable in sizes that are commonly used on farms and other outdoor applications. Do need to watch out so you don't apply one of those to an application that does enter a building. URD is stocked in dual rated conductors for more common sizes used to feed smaller services, like 2 AWG, 1/0, 2/0, 4/0 and 250 kcmil triplex (most ...
Submittal Reviews: Concentric Neutral and URD/UD
2013年3月14日 · 3) Correct, you do not need to run a seperate neutral conductor on concentric neutral cable. You would have to for shielded cable if it were used on a Wye system 4) 1/3 neutral is for three phase applications. (1/3*3=1) Full neutral is used for single phase or V phase applications. It can be used for three phase also, it just costs more. 5) UD=URD
Proper way to bury URD Cable? | Information by Electrical …
2021年7月12日 · One electrician was adamant about skipping URD and using regular wire inside PVC conduit. He said that he repairs breaks nonstop and I will have issues in a few years. One 10' stick of 2.5" conduit is $45 bucks at Lowes right now. I can't afford to not use URD.