Convert Kwh to KVA - OnlineConversion Forums
How to convert 1,000-kwh to KVA assuming the power source is at 380-volt, 3-phase, 50-hertz and power factor at 0.85.
Diesel Generator kWh produced - OnlineConversion Forums
2014年7月15日 · If I assume the sum of the three line currents is 9 A, and power factor = 1, you are generating about 2000 W (2 kW). For a better estimate, measure current on line 3 and plug into method above. If you only had line to line voltage, divide it by the square root of 3 to approximate line to neutral.
how do i convert kva to kwh - OnlineConversion Forums
2011年8月29日 · You need to know the power factor or phase angle to convert kVA to kW (multiply by the power factor or by the cosine of the phase angle. Second, you need to know the hours run at that power level to get kWh, which is a unit of energy not a unit of power.
Convert kVA to kWh - OnlineConversion Forums
2013年9月13日 · Depending on power factor, 500 kVA is a maximum of 500 kW, less if the power factor is less than unity. For kWh, you have to load in kilowatts and run time in hours.
Diesel Generator to KWH - OnlineConversion Forums
2009年3月12日 · You probably mean you have a 500 kW generator. That is a power rating. The energy is that power times the hours run. But in an hour it will produce 500 kWh 1 kWh = 3.6 MJ, so 500 kWh = 1.8 GJ Diesel has an energy content (higher heating value) of 137380 BTU/gal according to to US DoE. That converts to 38.29 MJ/L.
Convert KWh to Volt Amps - OnlineConversion Forums
2010年4月30日 · Welcome to the OnlineConversion.com forums. Due to changes in this version of the forum software, you are now required to register before you may post.
how to convert kVA into kg/hr - OnlineConversion Forums
2008年6月5日 · Very few would achieve 35%, and 25% would be relatively poor, except for small generators (<10 kW), which might even be around 20%. #2 diesel runs about 42.8 MJ/kg (LHV). If consuming 1 kg/h, you could generate about 12.8 MJ or 3.56 kW. The owner's manual usually gives some idea of fuel consumption at rated load.
Amps To Kilowatts - OnlineConversion Forums
Search in titles only Search in Convert and Calculate only. Search. Advanced Search
how to convert amps into kwh usage - OnlineConversion Forums
2007年9月22日 · If I multiply the volt*ampere rating, I get 3*230 V*26 A = 17940 VA = 17.94 kVA. However, if I assume the voltage is line-to-line and divide by the square root of 3, I get 10.4 kVA. If the power factor is close to 1, then it is also 10.4 kW. Just multiply by …
KVA vs KWH - OnlineConversion Forums
Welcome to the OnlineConversion.com forums. Due to changes in this version of the forum software, you are now required to register before you may post.
- 某些结果已被删除