Is Sprinkler Obstructed by Duct? - MeyerFire
2017年9月27日 · The sprinkler is centered above the duct. NFPA 13 (2016 Edition) has the 3x rule (8.6.5.2.1.3) which only applies to structural members in light and ordinary occupancies, and the duct is not over 4-feet wide which would require sprinklers by 8.6.5.3.3.
Sprinklers under ducts - NFPA (fire) Code Issues - Eng-Tips
2024年1月19日 · Assuming we abide to NFPA 13, the sprinkler deflector above the duct will most likely be even less than 25 cm which means that you need to apply the three-times rule for obstructions lying in the first 18 in (46 cm) vertically from deflector.
Sprinkler Installation Under Duct - NFPA (fire) Code Issues
2020年12月19日 · Sprinklers shall not be required under noncombustible obstructions over 4 ft (1.2 m) wide where the bottom of the obstruction is 24 in. (600 mm) or less above the floor or deck. In my question I asked 80cm width of duct that is because in our project we protect ducts which have the width of higher than 80cm. Best regards.
Fire Sprinkler Obstructions: The Rules for Nonstructural Objects
2023年6月7日 · The above item contrasts with continuous obstructions (3.3.140.1), such as soffits, beams, or ducts, which block water spray from two or more adjacent sprinklers. Storage is an obstruction category covered more in-depth by NFPA 25: Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems.
Sprinkler Head Obstruction Distance Rules: Standard Spray Fire
2019年7月11日 · In a nutshell, NFPA 25: Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems says that objects that can block a sprinkler’s spray must be at least 18 inches away from the deflector. (That’s the …
Sprinkler installations and obstructions | Consulting
2019年4月18日 · Learn about the different types of sprinklers used in building and life safety protection. Understand various obstructions to sprinkler-discharge patterns. Follow correct measures to mitigate or eliminate obstructions and ensure complete sprinkler coverage.
Vertical & Lateral Sprinkler Spacing Near Ducts?
2024年4月23日 · Sprinkler below duct are there to protect the space below the obstruction only. The distance to the end wall is not applicable IN THIS CASE, since there is a significant distance from the wall. The next sprinkler into the page can be a …
Spray Booths - NFPA (fire) Code Issues | Eng-Tips
2009年2月9日 · 9.4.6* Sprinkler systems protecting stacks or ducts shall meet all of the following requirements: (1) Sprinklers shall be spaced no more than 3.7 m (12 ft) apart. (2) If exhaust ducts are manifolded, a sprinkler shall be located in the manifold at the junction of each exhaust duct with the manifold.
#147 – Significant Changes to the 2019 Edition of NFPA 13, Part 1
2019年2月14日 · After defining key terms and introducing general requirements, NFPA 13 begins where designers of fire sprinkler systems begin: with the water supply and piping. The standard continues with system types and sprinkler placement before considering installation requirements for sprinkler heads, valves, and piping.
Sprinkler protection under ducts : r/firePE - Reddit
2024年1月19日 · I have a question regarding sprinkler protection under ducts. I understand that if the duct is wider than 1 meter (4 ft) there needs to be a sprinkler under it but if the duct is just below the ceiling does there also need to be a sprinkler above the duct?
Applicable Code for Sprinklers in Dust Collection? - MeyerFire
2023年10月11日 · "Quick-response sprinklers shall not be permitted for use in extra hazard occupancies or other occupancies where there are substantial amounts of flammable liquids or combustible dusts." It's hard to tell from the floor but I believe at least some of the systems have quick response. (2) Is the dust collector ductwork governed by NFPA 13 at all?
Fire Sprinkler Pipe: How to Perform an Obstruction Investigation
2019年11月15日 · In this first installment of our two-part series on fire sprinkler obstruction investigations, we describe when to investigate and some common sources of obstructions. Read part two next, where we discuss how inspections should be carried out and the standard flushing remedies to unblock sprinkler pipes. Looking to repair or replace obstructed ...
Sprinkler proximity to AC diffuser etc - NFPA (fire) Code Issues
2010年6月24日 · The requirement seems to address unwanted discharge of sprinklers caused by overheat, but doesn seem to address reduced response time caused by blowing cold air on a sprinkler as diffusers that only have cold air are exempt.
Pipe Obstructions in Fire Sprinkler Systems | NFSA
2020年11月3日 · Replacing pressurized air with nitrogen in dry sprinkler pipes can help prevent corrosion by removing the presence of oxygen, a critical leg of the corrosion triangle. Dry air generators employing a desiccant-based compressor/air exchanger that dehumidifies the air in the pipe are another option.
Sprinkler Required in Dust Collection Ductwork? - MeyerFire
2021年1月29日 · Premanufactured nozzle/sprinkler locations may be required on the units/ duct themselves. The detection and system unit design will also help dictate which type of applicable extinguishing agent will be required as well.
How close can light fixtures be to fire sprinkler heads?
2011年8月14日 · The residential code says pendant sprinklers must be at least 3 ft from obstructions such as ceiling fans and lights (as measured from their centers), or you can use this table which relates A) the distance from the sprinkler to the near edge of the obstruction and B) height of the sprinkler's deflector above the bottom of the obstruction.
Fire Sprinkler Pipe: How to Perform an Obstruction Investigation …
2019年11月19日 · In this blog, we examine how inspections should be carried out and outline standard flushing remedies to unblock fire sprinkler pipes. Looking to repair or replace obstructed pipes? Browse our selection of pipe and accessories, including CPVC pipe components, pipe hangers, and seismic bracing.
Does a Duct Near Ceiling Need Sprinkler Above? - MeyerFire
2024年1月31日 · Plain reading of code says yes. You might be able to convince an AHJ that its not necessary in non combustible construction. A few points to keep in mind: the possibility of a fire inside the duct, more probable activation of the sprinkler due to the height, and the protection of the structure in relation to escape time for the occupants.
The Minimum Distance From a Sprinkler Head to the Air
Sprinklers placed near air supply registers must have a higher temperature rating than typical sprinklers. This will keep the sprinkler from being accidentally set off by a blast of heat from a heater duct. Regular sprinklers set off at temperatures between 135 and 175 degrees Fahrenheit.
Duct under sprinkler - NFPA (fire) Code Issues - Eng-Tips
2008年11月11日 · Is it possible to put an pendent under and off to the side of a large duct? I would be putting an upright at a higher elevation, dropping the deflector of the pendent just below the bottom of the duct and providing a water shield.